Voltage Drop Calculator
Calculate voltage drop across cables and wires for copper and aluminum conductors.
Component Values
Results
AWG Wire Size Reference
| AWG | mm² | Copper (Ω/km) | Aluminum (Ω/km) |
|---|---|---|---|
| 10 | 5.261 | 3.19 | 5.04 |
| 12 | 3.309 | 5.08 | 8.01 |
| 14 | 2.081 | 8.07 | 12.73 |
| 16 | 1.309 | 12.83 | 20.24 |
| 18 | 0.823 | 20.41 | 32.20 |
| 20 | 0.518 | 32.43 | 51.16 |
| 22 | 0.326 | 51.53 | 81.29 |
| 24 | 0.205 | 81.95 | 129.27 |
| 26 | 0.129 | 130.23 | 205.43 |
| 28 | 0.081 | 207.41 | 327.16 |
| 30 | 0.0509 | 330.06 | 520.63 |
Understanding voltage drop in cables
Voltage drop is the reduction in voltage across a conductor due to its resistance. Every wire has resistance proportional to its length and inversely proportional to its cross-sectional area. The total cable resistance for a round-trip circuit is R = p x 2L / A, where p is the material resistivity, L is the one-way length, and A is the cross-section.
The IEC 60364 standard recommends that voltage drop should not exceed 3% for lighting circuits and 5% for other loads. The NEC similarly recommends 3% for branch circuits and 5% total. Excessive voltage drop wastes energy as heat in the cable and can cause equipment to malfunction, especially motors and sensitive electronics.
Copper (p = 1.68e-8 ohm.m) is the most common conductor material due to its low resistivity. Aluminum (p = 2.65e-8 ohm.m) has about 60% higher resistivity but is lighter and cheaper, making it popular for overhead power lines and large installations. To compensate, aluminum cables use a larger cross-section than copper for the same current capacity.
For long cable runs -- solar panel arrays, industrial plants, EV charging stations -- voltage drop calculation is critical. Increasing wire gauge (larger cross-section) reduces resistance and voltage drop. The trade-off is cost and weight. Always verify that your cable sizing satisfies both current capacity (ampacity) and voltage drop requirements.
Cable Resistance
R_cable = ρ × 2L / AVoltage Drop
V_drop = I × R_cableDrop Percentage
Drop% = (V_drop / V_source) × 100Key Points
- Voltage drop is proportional to current and cable length
- IEC 60364: max 3% for lighting, 5% for other circuits
- Copper has ~40% less resistivity than aluminum
- Doubling the cross-section halves the voltage drop
- Round-trip length = 2 x one-way cable length
Applications
- Residential and commercial wiring design
- Solar panel array cable sizing
- EV charging station installation
- Industrial plant power distribution
AWG quick-reference table (copper wire)
| AWG | Diameter (mm) | Area (mm²) | Max Current (A) | Resistance (mΩ/m) |
|---|---|---|---|---|
| 10 | 2.59 | 5.26 | 30 | 3.28 |
| 12 | 2.05 | 3.31 | 20 | 5.21 |
| 14 | 1.63 | 2.08 | 15 | 8.28 |
| 16 | 1.29 | 1.31 | 13 | 13.2 |
| 18 | 1.02 | 0.82 | 10 | 20.9 |
| 20 | 0.81 | 0.52 | 7 | 33.2 |
| 22 | 0.64 | 0.33 | 5 | 52.9 |
| 24 | 0.51 | 0.20 | 3 | 84.2 |
NEC / IEC voltage drop guideline
NEC/IEC guideline: voltage drop should not exceed 3% for branch circuits or 5% total (feeder + branch combined). For sensitive electronics — microcontrollers, sensors, audio — keep drop below 2% to avoid measurement errors and logic instability.
Practical example
Calculate round-trip voltage drop for a 5-metre LED strip cable run using 18 AWG copper wire.
R = 2 × 5m × 20.9 mΩ/m = 209 mΩ
Drop = 3A × 0.209Ω = 0.63V (5.2%) — exceeds 5% limit
Solution: upgrade to 16 AWG (13.2 mΩ/m) → drop = 0.40V (3.3%)
The factor of 2 everyone forgets
The mistake everyone makes is forgetting the factor of 2. Current leaves the source, runs down the wire to the load, and comes all the way back — so the copper it travels through is twice the one-way length. Drop the 2 and your calculated drop is half of reality, which is exactly the error that leaves an LED strip dim at the far end.
Voltage drop (round trip)
Vdrop = 2 × ρ × L × I / AL is the one-way run; the 2 covers the return leg. ρ_copper = 1.68×10⁻⁸ Ω·m at 20 °C, aluminium = 2.82×10⁻⁸ Ω·m — aluminium needs about 60% more cross-section to match copper.
AWG to mm² reference (copper resistance)
European installers spec cable in mm², American ones in AWG, and a voltage-drop number means nothing until you've pinned the cross-section. The copper resistance column is the one-way mΩ per metre at 20 °C — double it for the round trip in the formula above.
| AWG | mm² | Copper (mΩ/m) |
|---|---|---|
| 10 | 5.26 | 3.28 |
| 12 | 3.31 | 5.21 |
| 14 | 2.08 | 8.29 |
| 16 | 1.31 | 13.2 |
| 18 | 0.823 | 21.0 |
| 20 | 0.518 | 33.3 |
| 22 | 0.326 | 52.9 |
| 24 | 0.205 | 84.2 |
Need the full AWG list with ampacity and aluminium figures? The wire gauge calculator has it, and the resistor power calculator tells you how much heat that I²R drop actually dumps into the cable. The numbers above come straight from the American wire gauge standard.
The 3% rule and temperature derating
Electrical codes draw the line at 3%: keep the drop on any branch circuit at or below 3%, and the whole run — feeder plus branch — under 5%. For a 12 V system that 3% is only 0.36 V, which is why low-voltage runs eat cable so fast.
And the table values are cold values. Copper resistivity rises about 0.39% per °C, so a cable sitting at 70 °C — bundled in conduit on a hot day, or carrying near-rated current — has roughly 20% more resistance than the 20 °C number suggests. Size for the temperature the cable will actually run at, not the bench.
Worked examples
A 5 m feed in 18 AWG (21.0 mΩ/m). Watch the round trip bite into a tight 12 V budget.
Vdrop = 2 × 5 m × 0.021 Ω/m × 2 A = 0.42 V (3.5%)
Over the 3% line. Step up to 16 AWG (13.2 mΩ/m) → 0.26 V (2.2%).
A fridge or fan wired from the battery to the back of an RV. Long automotive 12 V runs are where this hurts.
16 AWG: 2 × 6 m × 0.0132 Ω/m × 8 A = 1.27 V (10.6%) — far too much.
Use 12 AWG (5.21 mΩ/m) → 0.50 V (4.2%).
A 12 V panel feeding a PWM controller 10 m away. Long, low-voltage runs are exactly where drop steals your harvest.
10 AWG (3.28 mΩ/m): 2 × 10 m × 0.00328 Ω/m × 6 A = 0.39 V (3.3%)
Acceptable, but an MPPT controller at higher array voltage would cut the percentage hard.
Did you know? Voltage drop in long cable runs is a critical issue in solar installations and marine/automotive wiring. A 10 m run of AWG 18 wire at 5 A can drop nearly 1 V — enough to cause a 5 V microcontroller to brown-out or an LED strip to visibly dim at the far end.