Rate this calculator

Voltage Drop Calculator

Calculate voltage drop across cables and wires for copper and aluminum conductors.

Component Values

V

Results

Cable Resistance (round trip)0.1344 Ω
Voltage Drop1.3440 V

AWG Wire Size Reference

AWGmm²Copper (Ω/km)Aluminum (Ω/km)
105.2613.195.04
123.3095.088.01
142.0818.0712.73
161.30912.8320.24
180.82320.4132.20
200.51832.4351.16
220.32651.5381.29
240.20581.95129.27
260.129130.23205.43
280.081207.41327.16
300.0509330.06520.63

Understanding voltage drop in cables

Voltage drop is the reduction in voltage across a conductor due to its resistance. Every wire has resistance proportional to its length and inversely proportional to its cross-sectional area. The total cable resistance for a round-trip circuit is R = p x 2L / A, where p is the material resistivity, L is the one-way length, and A is the cross-section.

The IEC 60364 standard recommends that voltage drop should not exceed 3% for lighting circuits and 5% for other loads. The NEC similarly recommends 3% for branch circuits and 5% total. Excessive voltage drop wastes energy as heat in the cable and can cause equipment to malfunction, especially motors and sensitive electronics.

Copper (p = 1.68e-8 ohm.m) is the most common conductor material due to its low resistivity. Aluminum (p = 2.65e-8 ohm.m) has about 60% higher resistivity but is lighter and cheaper, making it popular for overhead power lines and large installations. To compensate, aluminum cables use a larger cross-section than copper for the same current capacity.

For long cable runs -- solar panel arrays, industrial plants, EV charging stations -- voltage drop calculation is critical. Increasing wire gauge (larger cross-section) reduces resistance and voltage drop. The trade-off is cost and weight. Always verify that your cable sizing satisfies both current capacity (ampacity) and voltage drop requirements.

Cable Resistance

R_cable = ρ × 2L / A

Voltage Drop

V_drop = I × R_cable

Drop Percentage

Drop% = (V_drop / V_source) × 100

Key Points

  • Voltage drop is proportional to current and cable length
  • IEC 60364: max 3% for lighting, 5% for other circuits
  • Copper has ~40% less resistivity than aluminum
  • Doubling the cross-section halves the voltage drop
  • Round-trip length = 2 x one-way cable length

Applications

  • Residential and commercial wiring design
  • Solar panel array cable sizing
  • EV charging station installation
  • Industrial plant power distribution

AWG quick-reference table (copper wire)

AWGDiameter (mm)Area (mm²)Max Current (A)Resistance (mΩ/m)
102.595.26303.28
122.053.31205.21
141.632.08158.28
161.291.311313.2
181.020.821020.9
200.810.52733.2
220.640.33552.9
240.510.20384.2

NEC / IEC voltage drop guideline

NEC/IEC guideline: voltage drop should not exceed 3% for branch circuits or 5% total (feeder + branch combined). For sensitive electronics — microcontrollers, sensors, audio — keep drop below 2% to avoid measurement errors and logic instability.

Practical example

12V LED strip — 3A, 5m run (18 AWG copper)

Calculate round-trip voltage drop for a 5-metre LED strip cable run using 18 AWG copper wire.

R = 2 × 5m × 20.9 mΩ/m = 209 mΩ
Drop = 3A × 0.209Ω = 0.63V (5.2%) — exceeds 5% limit
Solution: upgrade to 16 AWG (13.2 mΩ/m) → drop = 0.40V (3.3%)

Did you know? Voltage drop in long cable runs is a critical issue in solar installations and marine/automotive wiring. A 10 m run of AWG 18 wire at 5 A can drop nearly 1 V — enough to cause a 5 V microcontroller to brown-out or an LED strip to visibly dim at the far end.